Two separate power faults at Sengkang Depot Substation led to disruptions on the North East Line (NEL) and Sengkang-Punggol LRT (SPLRT) on August 12 and 15. Investigations are ongoing to determine the root causes of the faults, and remedial measures are being implemented to prevent future occurrences.

Two power faults occurred at the voltage transformer for Switchboard 2 at Sengkang Depot Substation, disrupting train services on the North East Line (NEL) and the Sengkang-Punggol LRT (SPLRT) on August 12 and 15. According to a joint statement by the Land Transport Authority (LTA) and SBS Transit (SBST), the first fault on August 12 involved a high current surge due to a problem in the voltage transformer.

Subsequently, a cable connecting to the transformer dislodged, allowing current to continue flowing despite the blown fuse. This high current surge damaged Switchboard 2, and because the two switchboards were interconnected, Switchboard 1 disconnected from the system to prevent further damage. Services on both the NEL and SPLRT were gradually restored that day using a backup power supply. However, the extensive damage to Switchboard 2 meant it couldn't be immediately repaired. As Switchboard 1 remained undamaged, it was reconnected to resume normal service the following morning. LTA and SBST reported that repairs to the voltage transformer and Switchboard 2 were completed on August 16.On August 15, a power cable fault occurred on the SPLRT system. Since Switchboard 2 was still out of service from the August 12 incident, this fault caused the entire network to lose power. LTA and SBST stated that they are continuing to investigate the cause of the cable fault. They are also testing 28km of cables throughout the SPLRT network to assess their condition. These tests are expected to be finished by August 23 as they can only be conducted during engineering hours. As a long-term solution, LTA will be implementing a secondary power supply source directly from the SP Power Grid, scheduled to be completed by the fourth quarter of 2025 as part of the Sengkang Depot expansion. LTA is also collaborating with SBS Transit to make further upgrades to the power supply for the NEL and SPLRT

We have summarized this news so that you can read it quickly. If you are interested in the news, you can read the full text here. Read more:

asiaonecom /  🏆 10. in SG

Power Faults North East Line Sengkang-Punggol LRT Singapore Transportation Disruptions Land Transport Authority

 

Singapore Latest News, Singapore Headlines

Similar News:You can also read news stories similar to this one that we have collected from other news sources.

NEL disruption: Main and backup power supply tripped at depot substationNEL disruption: Main and backup power supply tripped at depot substationThe power fault led to a three-hour disruption of train services on the North East Line.
Read more »

North-East Line, Sengkang-Punggol LRT resume train services after power faultNorth-East Line, Sengkang-Punggol LRT resume train services after power faultTrain services on the North-East Line and the Sengkang-Punggol LRT are back to normal. Power has been safely restored to the affected depot substation, following a power fault that disrupted services for several hours on Tuesday.
Read more »

Power fault on Sengkang-Punggol LRT line: Service fully restored, says SBS TransitPower fault on Sengkang-Punggol LRT line: Service fully restored, says SBS TransitServices on the Sengkang-Punggol LRT (SPLRT) have been fully restored by about 12.30pm, said SBS Transit. Free regular bus and bridging bus services have stopped. This comes after train service on the SPLRT was disrupted earlier this morning (Aug 15) due to a power fault.
Read more »

Full service on Sengkang-Punggol LRT resumes after four-hour disruption due to power faultFull service on Sengkang-Punggol LRT resumes after four-hour disruption due to power faultSBS Transit Group CEO Jeffrey Sim says the incident was worsened by damage to the back-up switchboard from the previous breakdown on Aug 12.
Read more »

Four-hour power fault cripples Sengkang-Punggol LRT: Commuters voice growing frustrationFour-hour power fault cripples Sengkang-Punggol LRT: Commuters voice growing frustration%
Read more »

NEL, Sengkang-Punggol LRT disruptions stemmed from rare 'double fault' scenario: LTA and SBS TransitNEL, Sengkang-Punggol LRT disruptions stemmed from rare 'double fault' scenario: LTA and SBS TransitThe disruptions to the North East Line and the Sengkang-Punggol LRT (SPLRT) lines on Aug 12 was due to a 'double fault' scenario which occurred in a voltage transformer for one of two interconnected switchboards at the Sengkang Depot Substation — an occurrence described as 'rare'.
Read more »